Wire size calculator

Wire size calculator

System, load, voltage, length and maximum drop: you get the minimum copper size by comparing voltage drop with ampacity, plus AWG equivalents.

Deterministic calculation in your browser. No signup to see the result.

Minimum wire size

4 mm²

  • Minimum copper cross-section4 mm²
  • Current25 A
  • Size by voltage drop4 mm²
  • Size by ampacity4 mm²

Your prices per language/currency. Used when you enable “Use my prices” in calculators. My prices →

Calculate labour, margin & VAT

How it's calculated (visible formula)

A_drop = k × L × I × PF ÷ (γ × VD_max); size = max(drop size; ampacity size)

See methodology and formula versions

How to calculate it, step by step

  1. Work out circuit current from the load.
  2. Measure the run length.
  3. Set the maximum voltage drop (3% typical).
  4. Size by voltage drop and by ampacity.
  5. Take the larger and check the breaker protects it.

Metric sizes and AWG equivalents

Metric sizes and AWG equivalents
mm²Ampacity (1-ph / 3-ph, PVC in conduit)≈ AWG
1.515 / 13.5 A15–14
2.521 / 18.5 A13–12
427 / 24 A11–10
636 / 32 A9–8
1050 / 44 A7–6
1666 / 59 A5–4
2584 / 77 A3–2
35104 / 96 A1

Worked example: 5,750 W at 230 V, 66 ft, 3% max drop

  1. I = 25 A
  2. By drop: 3.0 mm² → 4 mm²
  3. By ampacity: 25 A → 4 mm²

→ 4 mm² copper (≈ 10–11 AWG; use 10 AWG).

Common mistakes

Pro tips

From calculation to quote

Add labour, overhead and your margin, and generate the professional PDF.

FAQs

What size wire for 20 amps?
12 AWG copper for a typical 20 A branch circuit.
What size wire for 30 amps?
10 AWG copper, upsized for long runs.
Why metric sizes?
This tool uses IEC sizes and tables; the table shows the nearest AWG. Confirm with NEC 310.16.
What wire for a 50 A electric range?
6 AWG copper on a 50 A breaker.
What wire for lighting?
14 AWG on 15 A or 12 AWG on 20 A.
Can 12 AWG go on a 30 A breaker?
No — 12 AWG copper is generally limited to 20 A protection.