Heat pump balance point calculator
Design load, design and indoor temperatures, and heat pump capacity at 7 °C and −7 °C (45 °F and 19 °F): you get the balance point and backup heat at design conditions.
Backup heat at design temperature
7301.983 BTU/h
- Balance point-0.7 °C
- Load at balance point22588.378 BTU/h
- Heat pump capacity at design temperature19995.15 BTU/h
- Backup heat needed at design temperature7301.983 BTU/h
Your prices per language/currency. Used when you enable “Use my prices” in calculators. My prices →
How it's calculated (visible formula)
load(T) = design load × (Ti − T) ÷ (Ti − Td); capacity linear between 7 °C and −7 °C; balance where load = capacity
- Net geometric measurement, no waste.
- Adjustable waste % for cuts and breakage.
- Purchase rounded up to sellable units (boxes, bags, buckets, boards).
How to calculate it, step by step
- Work out the heating load at outdoor design temperature.
- Set the indoor setpoint.
- Look up heat pump capacity at 47 °F and 17 °F (or 7 °C / −7 °C).
- Find where load and capacity meet.
- Work out backup heat needed on the coldest day.
Worked example: 8 kW load at 23 °F (−5 °C), 68 °F indoors, 8 kW at 45 °F and 5.5 kW at 19 °F
- Load: 0.32 kW per °C
- Capacity: 5.5 + 0.179 × (T + 7)
- Equal at −0.7 °C
→ Balance point ≈ 31 °F; at 23 °F you need 2.1 kW (7,300 BTU/h) of backup.
Common mistakes
- Using rated 47 °F capacity all winter.
- Ignoring defrost cycles below about 40 °F.
- Using another region's design temperature.
Pro tips
- In cold climates choose a cold-climate certified model.
- Backup can be electric strips or the existing furnace.
- Shelter the outdoor unit from wind and allow defrost drainage.
- Better insulation lowers the balance point and backup need.
From calculation to quote
Add labor, overhead and your margin, and generate the professional PDF.
FAQs
- What is the balance point?
- The outdoor temperature where heat pump output exactly meets the home's heat loss.
- Where do I find capacity at 17 °F?
- In the AHRI/NEEP cold-climate listing or the maker's extended tables.
- What design temperature should I use?
- The ASHRAE 99% heating design temperature for your location.
- Why does capacity drop in the cold?
- There's less heat to extract from colder air.
- Is a high balance point bad?
- It means more hours on backup and higher bills.
- How much does strip heat cost?
- 1 kW of strip heat uses 1 kW; a heat pump uses 2–4× less per kW of heat.