Retaining wall pressure calculator

Retaining wall pressure calculator

Wall height, soil unit weight, friction angle and surcharge: you get Ka, soil and surcharge thrust, the resultant height and the overturning moment.

Deterministic calculation in your browser. No signup to see the result.

Total active thrust

18.67 kN/m

  • Active pressure coefficient Ka0.33
  • Soil thrust12 kN/m
  • Surcharge thrust6.67 kN/m
  • Resultant height above base2.592 ft
  • Overturning moment at base14.67 kN·m/m

Your prices per language/currency. Used when you enable “Use my prices” in calculators. My prices →

Calculate labor, margin & tax

How it's calculated (visible formula)

Ka = tan²(45° − φ/2); Pa = ½·Ka·γ·H² + Ka·q·H; M = ½·Ka·γ·H²·H/3 + Ka·q·H·H/2

See methodology and formula versions

How to calculate it, step by step

  1. Set the total retained soil height.
  2. Take soil unit weight and friction angle (ideally from a soils report).
  3. Compute Ka = tan²(45° − φ/2).
  4. Compute the triangular soil thrust and rectangular surcharge thrust.
  5. Get the resultant, its height and the overturning moment to check the wall.

Typical soil parameters

Typical soil parameters
Soilγ (kN/m³)φ
Loose sand1730°
Dense sand1935°
Gravel1938°
Stiff clay1922°

Worked example: 6.5 ft (2 m) wall, γ = 18 kN/m³, φ = 30°, q = 10 kN/m²

  1. Ka = tan²(30°) = 0.333
  2. Soil: ½ × 0.333 × 18 × 2² = 12 kN/m
  3. Surcharge: 0.333 × 10 × 2 = 6.67 kN/m

→ Pa = 18.67 kN/m (≈1,280 lb/ft); base moment ≈ 14.7 kN·m/m.

Common mistakes

Pro tips

From calculation to quote

Add labor, overhead and your margin, and generate the professional PDF.

FAQs

What is Ka?
The active earth pressure coefficient: the share of vertical soil pressure passed to a wall that yields slightly.
What friction angle should I use?
Sands 30–35°, gravels 35–40°, clays 20–25°. Use your geotechnical report when you have one.
Can I design the wall with this?
It's a preliminary check; overturning, sliding and bearing checks are done by an engineer.
What surcharge for a parking area?
Roughly 250 psf (12 kPa) for light vehicles is a common assumption; follow your local code.
What is at-rest pressure?
Pressure on a wall that can't move; higher than active pressure.
Where does the resultant act?
At H/3 above the base for soil and H/2 for uniform surcharge.