Conduit fill calculator

Conduit fill calculator

Number of conductors and size: you get the minimum conduit that stays under 40% fill and the actual fill percentage.

Deterministic calculation in your browser. No signup to see the result.

Minimum conduit

16 mm Ø

  • Minimum conduit (outside diameter)16 mm Ø
  • Fill of that conduit33.96 %
  • Area taken by conductors30.54 mm²

Your prices per language/currency. Used when you enable “Use my prices” in calculators. My prices →

Calculate labour, margin & GST

How it's calculated (visible formula)

fill = Σ π/4 × d_wire² ÷ (π/4 × d_conduit,inside²) ≤ 40%

See methodology and formula versions

How to calculate it, step by step

  1. Count conductors in the conduit, including grounds.
  2. Choose conductor size.
  3. Add up the cross-section of all wires.
  4. Find the conduit whose inside area keeps fill at 40% or less.
  5. Check bends and pull-box spacing.

Worked example: 3 conductors of 2.5 mm² (≈ 12 AWG)

  1. 3 × π/4 × 3.6² = 30.5 mm²
  2. 16 mm conduit (10.7 mm ID): 34% fill

→ 16 mm (½ in trade size) conduit.

Common mistakes

Pro tips

From calculation to quote

Add labour, overhead and your margin, and generate the professional PDF.

FAQs

What is the 40% rule?
NEC Chapter 9 limits fill to 40% for three or more conductors.
Does the ground count?
Yes, equipment grounding conductors count toward fill.
What about EMT or PVC?
Inside diameters differ; this tool uses corrugated conduit sizes.
How many 12 AWG wires in ½ in EMT?
Up to nine THHN conductors per NEC Annex C.
EMT or PVC?
EMT indoors; PVC underground or in wet locations.
Does the neutral count toward fill?
Yes — every conductor counts.